Internet-Draft Requirements for Energy Efficiency October 2024
Stephan, et al. Expires 24 April 2025 [Page]
Workgroup:
Getting Ready for Energy-Efficient Networking
Internet-Draft:
draft-stephan-green-ucs-and-reqs-00
Published:
Intended Status:
Informational
Expires:
Authors:
E. Stephan
Orange
M. Palmero
Cisco Systems, Inc.
B. Claise
Huawei
Q. Wu
Huawei
L. M. Contreras
Telefonica

Requirements for Energy Efficiency Management

Abstract

This document delineates the requirements for standards specifications in Energy Efficiency Management, extending the foundational work of RFC6988 and incorporating recent insights from operator requirements and the GREEN BoF discussions. Eleven years after the publication of RFC6988, this document reassesses and updates the requirements to align with contemporary needs.

The primary objectives of this draft, which are listed in the goals and scope with the creation of the GREEN WG charter, is focusing on two main targets: (1) collecting and updating requirements for the management of energy-efficient networks, and (2) defining use cases for managing energy-efficient networks.

This draft merges two drafts: (draft-eman-green-rfc6988bis-01)[https://datatracker.ietf.org/doc/draft-eman-green-rfc6988bis/] and (draft-stephan-green-bof-reqs-collections-02)[https://datatracker.ietf.org/doc/draft-stephan-green-bof-reqs-collections/].

Discussion Venues

Source of this draft and an issue tracker can be found at https://github.com/emile22/draft-stephan-green-terms-ucs-and-reqs

About This Document

This note is to be removed before publishing as an RFC.

The latest revision of this draft can be found at https://emile22.github.io/draft-stephan-green-ucs-and-reqs/draft-stephan-green-ucs-and-reqs.html. Status information for this document may be found at https://datatracker.ietf.org/doc/draft-stephan-green-ucs-and-reqs/.

Discussion of this document takes place on the Getting Ready for Energy-Efficient Networking Working Group mailing list (mailto:green@ietf.org), which is archived at https://mailarchive.ietf.org/arch/browse/green/. Subscribe at https://www.ietf.org/mailman/listinfo/green/.

Source for this draft and an issue tracker can be found at https://github.com/emile22/draft-stephan-green-ucs-and-reqs.

Status of This Memo

This Internet-Draft is submitted in full conformance with the provisions of BCP 78 and BCP 79.

Internet-Drafts are working documents of the Internet Engineering Task Force (IETF). Note that other groups may also distribute working documents as Internet-Drafts. The list of current Internet-Drafts is at https://datatracker.ietf.org/drafts/current/.

Internet-Drafts are draft documents valid for a maximum of six months and may be updated, replaced, or obsoleted by other documents at any time. It is inappropriate to use Internet-Drafts as reference material or to cite them other than as "work in progress."

This Internet-Draft will expire on 24 April 2025.

Table of Contents

1. Introduction

This document delineates the requirements for standards specifications in Energy Efficiency Management, extending the foundational work of RFC6988 and incorporating recent insights from operator requirements and the GREEN BoF discussions. Eleven years after the publication of RFC6988, this document reassesses and updates the requirements to align with contemporary needs.

The primary objectives of this draft, which are listed in the goals and scope with the creation of the GREEN WG charter, is focusing on two main targets: (1) collecting and updating requirements for the management of energy-efficient networks, and (2) defining use cases for managing energy-efficient networks.

Requirements are segmented into three core functions: discovery, monitoring, and control. Discovery functions involve identifying energy-managed networks, devices, and their components, as well as discovering the inventory of power components capabilities, optimization control capabilities, and nominal condition use. Monitoring functions encompass tracking power states, power attributes, energy consumption, network performance, and energy efficiency metrics. Control functions include managing energy-saving and optimization functions and the power states of energy-managed devices and their components.

This document does not mandate specific use cases for compliant implementations but rather lists a few use cases that must be supported by standards for Energy Efficiency Management.

Terms and definitions related to energy efficiency metrics will be discussed in later stages for potential integration.

This draft merges two drafts: (draft-eman-green-rfc6988bis-01)[https://datatracker.ietf.org/doc/draft-eman-green-rfc6988bis/] and (draft-stephan-green-bof-reqs-collections-02)[https://datatracker.ietf.org/doc/draft-stephan-green-bof-reqs-collections/].

At this step the specifications made by the IETF, aka in WGs like EMAN, on energy managements focus mainly on SMI (aka MIBs) instead of YANG and cover neither the control nor energy efficiency. As a consequence, the willing of this document is to resuse pieces of the energy-related requirements of RFC6988 and to map them in a framework of YANG/Netconf for energy efficiency that might reuse "YANG Data Model for Hardware Management" [RFC8348], a conversion of former Entity MIB module, Entity Sensor MIB module, Entity State MIB modules.

The following section will delve into the specific details but from a high level point of view, the differences between this document and the RFC6988 are:

However, Power and Energy Monitoring and Control MIB modules has not been converted yet into YANG modules.

1.1. Background

With rising energy costs and an increasing awareness of the environmental impact of running information technology equipment, Energy efficiency Management functions and management interfaces are becoming an additional basic requirement for network management systems and devices connected to a network.

This document defines requirements for standards specifications for Energy efficiency Management, including discovery functions, monitoring functions and control functions. Energy efficiency Management functions focus mainly on network devices and their built-in components that receive and provide electrical energy. Devices such as switches, routers, servers and storage devices should have an IP address providing a management interface for the network device. Alternatively, energy-related devices (for example, in building management, which typically don't support IP) might be connected via a proxy/gateway with an IP address.

These requirements are concerned with the standards specification process and not the implementation of specified standards. All requirements in this document must be reflected by standards specifications to be developed. However, which of the features specified by these standards will be mandatory, recommended, or optional for compliant implementations is to be defined by Standards Track document(s) and not in this document.

Section 3 elaborates on a set of general needs for Energy Management. Requirements for an Energy Management standard are specified in Sections 4 through 8.

Sections 4 through 6 contain conventional requirements specifying information on entities and control functions.

Sections 7 and 8 contain requirements specific to Energy Management. Due to the nature of power supply, some monitoring and control functions are not conducted by interacting with the entity of interest but rather with other entities, for example, entities upstream in a power distribution tree.

1.2. Conventional Requirements for Energy Efficiency Management

The specification of requirements for an Energy Efficiency Management standard starts with Section 4, which addresses the identification of entities and the granularity of reporting of energy-related information. A standard must support the unique identification of entities, reporting per network, per entire device, and reporting energy-related information on individual components of a device or attached devices.

Section 5 specifies requirements related to the monitoring of entities. This includes general (type, context) information and specific information on Power States, Power Inlets, Power Outlets, power, energy. The control of Power State and power saving functionalities, optimization functionalities by entities is covered by requirements specified in Section 6.

1.3. Specific Requirements for Energy Management

While the conventional requirements summarized above seem to be all that would be needed for Energy Management, there are significant differences between Energy Management and most well-known network management functions. The most significant difference is the need for some devices to report on other entities. There are two major reasons for this.

o For monitoring a particular entity, it is not always sufficient to communicate only with that entity. When the entity has no instrumentation for determining power, it might still be possible to obtain power values for the entity via communication with other entities in its power distribution tree. A simple example of this would be the retrieval of power values from a power meter at the power line into the entity. A Power Distribution Unit (PDU) and a Power over Ethernet (PoE) switch are common examples. Both supply power to other entities at sockets or ports, respectively, and are often instrumented to measure power per socket or port. Also it could be considered to obtain power values for the entity via communication with other entities outside of the power distribution tree, like for example external databases or even data sheets.

o Similar considerations apply to controlling the power supply of an entity that often needs direct or indirect communications with another entity upstream in the power distribution tree. Again, a PDU and a PoE switch are common examples, if they have the capability to switch power on or off at their sockets or ports, respectively.

These specific issues of Energy Management, as well as other issues, are covered by requirements specified in Sections 7 and 8.

The requirements in these sections need a new Energy Management framework that deals with the specific nature of Energy Management. The actual standards documents, such as MIB module specifications, address conformance by specifying which features must, should, or may be implemented by compliant implementations.

2. Terminology

The terms below are a sub set of the whole terminology. There are many other drafts givving additionnal definitons.

The terms specified in the terminology section are capitalized throughout the document; the exceptions are the well-known terms "energy" and "power". These terms are generic and are used in generated terms such as "energy-saving", "low-power", etc.

Embedded carbon (or embodied carbon)

  The total amount of greenhouse gas emissions, measured in tonnes
  of CO2 equivalent (tCO2e), associated with the entire lifecycle
  of a product or material, from raw material extraction through
  manufacturing, transportation, use, and end-of-life disposal or
  recycling.

Embodied energy

  The total amount of energy consumed in all processes associated
  with the production of a building material or product, from the
  extraction and processing of raw materials, through manufacturing,
  transportation, and installation, to the end of its useful life,
  including disposal or recycling.

Energy

  Energy is the capacity of a system to do work.  As used by
  electric utilities, it is generally a reference to electrical
  energy and is measured in kilowatt-hours (kWh) [IEEE-100].

Power

  Power is the time rate at which energy is emitted, transferred, or
  received; power is usually expressed in watts (or in joules per
  second) [IEEE-100].  (The term "power" does not refer to the
  concept of demand, which is an averaged power value.)

Power Attributes

  Power Attributes are measurements of electric current, voltage,
  phase, and frequencies at a given point in an electrical power
  system (adapted from [IEC.60050]).

  NOTE: Power Attributes are not intended to be "judgmental" with
  respect to a reference or technical value and are independent of
  any usage context.

Energy Management

  Energy Management is a set of functions for measuring, modeling,
  planning, and optimizing networks to ensure that the network
  elements and attached devices use energy efficiently and in a
  manner appropriate to the nature of the application and the cost
  constraints of the organization [ITU-M.3400].

Energy Efficiency Management

 Involves deploying and managing network infrastructures with the
 goal of optimizing energy use on network devices while improving
 the overall network utilization.

Energy Management System

  An Energy Management System is a combination of hardware and
  software used to administer a network with the primary purpose
  being Energy Management.

Energy Monitoring

  Energy Monitoring is a part of Energy Efficiency Management that deals
  with collecting or reading information from network elements and their
  components to aid in Energy Efficiency Management.

Energy Control

  Energy Control is a part of Energy Management that deals with
  controlling energy supply and Power State of network elements, as
  well as their components.

Power Interface

  A Power Interface is an interface at which a device is connected
  to a power transmission medium, at which it can in turn receive
  power, provide power, or both.

Power Inlet

  A Power Inlet is a Power Interface at which a device can receive
  power from other devices.

Power Outlet

  A Power Outlet is a Power Interface at which a device can provide
  power to other devices.

Power State

  A Power State is a condition or mode of a device that broadly
  characterizes its capabilities, power consumption, and
  responsiveness to input [IEEE-1621].

4. Identification of Entities

Entities must be capable of being uniquely identified within the context of the management system. This includes entities that are components of managed devices as well as entire devices or the entire network.

Entities that report on or control other entities must identify the entities they report on or control: see Section 7 or Section 8, respectively, for the detailed requirements.

An entity may be an entire network, or network device or a component of it. Examples of components of interest are a hard drive, a fan, or a line card. The ability to control individual components to save energy may be required. For example, server blades can be switched off when the overall load is low, or line cards at switches may be powered down at night.

Identifiers for network, network devices and components are already defined in standard YANG modules Network Topology YANG module [RFC8345] and Hardware YANG module [RFC8348]. Note that Network Topology YANG module [RFC8345] identifiers are reused in the Network Inventory YANG module [I-D.ietf-ivy-network-inventory-yang] and are also the basis for the Digital Map Modeling efforts in the NMOP Working Group.

Instrumentation for measuring the received and provided energy of a device is typically more expensive than instrumentation for retrieving its Power State. Many devices may provide Power State information for all individual components separately, while reporting the received and provided energy only for the entire device.

4.1. Identifying Entities

The standard must provide means for uniquely identifying entities. Uniqueness must be preserved such that collisions of identities are avoided at potential receivers of monitored information.

4.2. Identifying Entitiy Capabilities

The standard must provide means for discovering inventory of power components together with their capabilities, optimization control capabilities, nominal condition use. In addition, The standard must provide means for discovering supported power state of each network device within the network and power relationship between component within network device and across network devices.

4.3. Persistence of Identifiers

The standard must provide means for indicating whether identifiers of entities are persistent across a restart of the entity.

4.4. Change of Identifiers

The standard must provide means to indicate any change of entity identifiers.

4.5. Using Entity Identifiers of Existing YANG Modules

The standard must provide means for reusing entity identifiers from existing standards, including at least the following:

o the network-id, link-id, node-id, port-id of the Network Topology YANG module [RFC8345]

o the ne-id, Universal Unique IDentifier (UUID) of the network element and component-id, UUID of each component within the network element in Network Inventory YANG module [I-D.ietf-ivy-network-inventory-yang]

o the name, UUID of each hardware component in the Hardware YANG module [RFC8348]

Generic means for reusing other entity identifiers must be provided.

5. Information on Entities

This section describes information on entities for which the standard must provide means for retrieving and reporting.

Required information can be structured into seven groups. Section 5.1 specifies requirements for general information on entities, such as type of entity or context information. Requirements for information on Power Inlets and Power Outlets of entities are specified in Section 5.2. The monitoring of power and energy is covered by Sections 5.3 and 5.5, respectively. Section 5.4 covers requirements related to entities' Power States. Finally, the reporting of time series of values is covered by Section 5.7.

5.1. General Information on Entities

For Energy Management, understanding the role and context of an entity may be required. An Energy Management System may aggregate values of received and provided energy according to a defined grouping of entities. When controlling and setting Power States, it may be helpful to understand the grouping of the entity and role of an entity in a network. For example, it may be important to exclude some mission-critical network devices from being switched to lower power or even from being switched off.

5.1.1. Type of Entity

The standard must provide means to configure, retrieve, and report a textual name or a description of an entity.

5.1.2. Context of an Entity

The standard must provide means for retrieving and reporting context information on entities, for example, tags associated with an entity that indicate the entity's role.

5.1.3. Significance of Entities

The standard must provide means for retrieving and reporting the significance of entities within its context, for example, how important the entity is.

5.1.4. Power Priority

The standard must provide means for retrieving and reporting power priorities of entities. Power priorities indicate an order in which Power States of entities are changed, for example, to lower Power States for saving power.

5.1.5. Grouping of Entities

The standard must provide means for grouping entities. This can be achieved in multiple ways, for example, by providing means to tag entities, assign them to domains, or assign device types to them.

5.2. Power Interfaces

A Power Interface is an interface at which a device is connected to a power transmission medium, at which it can in turn receive power, provide power, or both.

A Power Interface is either an inlet or an outlet. Some Power Interfaces change over time from being an inlet to being an outlet and vice versa. However, most Power Interfaces never change.

Network Devices have Power Inlets at which they are supplied with electric power. Most devices have a single Power Inlet, while some have multiple inlets. Different Power Inlets on a device are often connected to separate power distribution trees. For Energy Monitoring, it is useful to retrieve information on the number of inlets of a device, the availability of power at inlets, and which inlets are actually in use.

Network Devices can have one or more Power Outlets for supplying other devices with electric power.

For identifying and potentially controlling the source of power received at an inlet, identifying the Power Outlet of another network device at which the received power is provided may be required. Analogously, for each outlet, it is of interest to identify the Power Inlets that receive the power provided at a certain outlet. Such information is also required for constructing the wiring topology of electrical power distribution to devices.

Static properties of each Power Interface are required information for Energy Efficiency Management. Static properties include the kind of electric current (AC or DC), the nominal voltage, the nominal AC frequency, and the number of AC phases. Note that the nominal voltage is often not a single value but a voltage range, such as, for example, (100V-120V), (100V-240V), (100V-120V,220V-240V).

5.2.1. List of Power Interfaces

The standard must provide means for monitoring the list of Power Interfaces of a device.

5.2.2. Operational Mode of Power Interfaces

The standard must provide means for monitoring the operational mode of a Power Interface, which is either "Power Inlet" or "Power Outlet".

5.2.3. Corresponding Power Outlet

The standard must provide means for identifying the Power Outlet that provides the power received at a Power Inlet.

5.2.4. Corresponding Power Inlets

The standard must provide means for identifying the list of Power Inlets that receive the power provided at a Power Outlet.

5.2.5. Availability of Power

If the Power States allow it, the standard must provide means for monitoring the availability of power at each Power Interface. This includes indicating whether a power supply at a Power Interface is switched on or off.

5.2.6. Use of Power

The standard must provide means for monitoring each Power Interface if it is actually in use. For inlets, this means that the device actually receives power at the inlet. For outlets, this means that power is actually provided from the outlet to one or more devices.

5.2.7. Type of Current

The standard must provide means for reporting the type of current (AC or DC) for each Power Interface as well as for a device.

5.2.8. Nominal Voltage Range

The standard must provide means for reporting the nominal voltage range for each Power Interface.

5.2.9. Nominal AC Frequency

The standard must provide means for reporting the nominal AC frequency for each Power Interface.

5.2.10. Number of AC Phases

The standard must provide means for reporting the number of AC phases for each Power Interface.

5.3. Power

Power is measured as an instantaneous value or as the average over a time interval.

Obtaining highly accurate values for power and energy may be costly if dedicated metering hardware is required. Entities without the ability to measure with high accuracy their power, received energy, and provided energy may just report estimated values, for example, based on load monitoring, Power State, or even just the entity type.

Depending on how power and energy values are obtained, the confidence in a reported value and its accuracy will vary. Entities reporting such values should qualify the confidence in the reported values and quantify the accuracy of measurements. For reporting accuracy, the accuracy classes specified in IEC 62053-21 [IEC.62053-21] and IEC 62053-22 [IEC.62053-22] should be considered.

Further properties of the power supplied to a device are also of interest. For AC power supply in particular, several Power Attributes beyond the real power are of potential interest to Energy Management Systems. The set of these properties includes the complex Power Attributes (apparent power, reactive power, and phase angle of the current or power factor) as well as the actual voltage, the actual AC frequency, the Total Harmonic Distortion (THD) of voltage and current, and the impedance of an AC phase or of the DC supply. A new standard for monitoring these Power Attributes should be in line with already-existing standards, such as [IEC.61850-7-4].

For some network management tasks, it is desirable to receive notifications from entities when their power value exceeds or falls below given thresholds.

5.3.1. Real Power / Power Factor

The standard must provide means for reporting the real power for each Power Interface as well as for an entity. Reporting power includes reporting the direction of power flow.

5.3.2. Power Measurement Interval

The standard must provide means for reporting the corresponding time or time interval for which a power value is reported. The power value can be measured at the corresponding time or averaged over the corresponding time interval.

5.3.3. Power Measurement Method

The standard must provide means to indicate the method used to obtain these values. Based on how the measurement was conducted, it is possible to associate a certain degree of confidence with the reported power value. For example, there are methods of measurement such as direct power measurement, estimation based on performance values, or hard-coding average power values for an entity.

5.3.4. Accuracy of Power and Energy Values

The standard must provide means for reporting the accuracy of reported power and energy values.

5.3.5. Actual Voltage and Current

The standard must provide means for reporting the actual voltage and actual current for each Power Interface as well as for a device. For AC power supply, means must be provided for reporting the actual voltage and actual current per phase.

5.3.6. High-Power/Low-Power Notifications

The standard must provide means for creating notifications if power values of an entity rise above or fall below given thresholds.

5.3.7. Complex Power / Power Factor

The standard must provide means for reporting the complex power for each Power Interface and for each phase at a Power Interface. In addition to the real power, at least two of the following three quantities need to be reported: apparent power, reactive power, and phase angle. The phase angle can be substituted by the power factor.

5.3.8. Actual AC Frequency

The standard must provide means for reporting the actual AC frequency for each Power Interface.

5.3.9. Total Harmonic Distortion

The standard must provide means for reporting the Total Harmonic Distortion (THD) of voltage and current for each Power Interface. For AC power supply, means must be provided for reporting the THD per phase.

5.3.10. Power Supply Impedance

The standard must provide means for reporting the impedance of a power supply for each Power Interface. For AC power supply, means must be provided for reporting the impedance per phase.

5.4. Power State

Many entities have a limited number of discrete Power States.

There is a need to report the actual Power State of an entity and to provide the means for retrieving the list of all supported Power States.

Different standards bodies have already defined sets of Power States for some entities, and others are creating new Power State sets. In this context, it is desirable that the standard support many of these Power State standards. In order to support multiple management systems that possibly use different Power State sets while simultaneously interfacing with a particular entity, the Energy Management System must provide means for supporting multiple Power State sets used simultaneously at an entity.

Power States have parameters that describe their properties. It is required to have a standardized means for reporting some key properties, such as the typical power of an entity in a certain state.

There is also a need to report statistics on Power States, including the time spent as well as the received and provided energy in a Power State.

5.4.1. Actual Power State

The standard must provide means for reporting the actual Power State of an entity.

5.4.2. List of Supported Power States

The standard must provide means for retrieving the list of all potential Power States of an entity.

5.4.3. Multiple Power State Sets

The standard must provide means for supporting multiple Power State sets simultaneously at an entity.

5.4.4. List of Supported Power State Sets

The standard must provide means for retrieving the list of all Power State sets supported by an entity.

5.4.5. List of Supported Power States within a Set

The standard must provide means for retrieving the list of all potential Power States of an entity for each supported Power State set.

5.4.6. Typical Power Per Power State

The standard must provide means for retrieving the typical power for each supported Power State.

5.4.7. Power State Statistics

The standard must provide means for monitoring statistics per Power State, including the total time spent in a Power State, the number of times each state was entered, and the last time each state was entered. More Power State statistics are addressed by the requirements in Section 5.5.3.

5.4.8. Power State Changes

The standard must provide means for generating a notification when the actual Power State of an entity changes.

5.5. Energy

The monitoring of electrical energy received or provided by an entity is a core function of Energy Management. Since energy is an accumulated quantity, it is always reported for a certain interval of time. This can be, for example, the time from the last restart of the entity to the reporting time, the time from another past event to the reporting time, the last given amount of time before the reporting time, or a certain interval specified by two timestamps in the past.

It is useful for entities to record their received and provided energy per Power State and report these quantities.

In addition, it is also useful for entities to record energy attributes such as maximum wake up time, maximum sleep time, service interruption time, transition time, maximum packet throughput, maximum bit throughput and report these quantities.

5.5.1. Energy Measurement

The standard must provide means for reporting measured values of energy and the direction of the energy flow received or provided by an entity. The standard must also provide the means to report the energy passing through each Power Interface.

5.5.2. Energy Efficiency Measurement

The standard must provide means for measuring the trade-off between service-level object and energy consumption. [ETSI-ES-203-136], [ITUT-L.1310], [ATIS-0600015.03.2013] provide methodology and test procedure for measuring such energy efficiency related metrics, which is defined as the throughput forwarded by 1 watt. The traffic loads and the weighted multipliers need to be clearly established in advance.

Note that, based on the specific optimization policy (throughput, heat, energy source, etc.), different derived metrics should be computed at the controller level.

5.5.3. Power Gain Measurement

The standard must provide means for measuring power gain, which can be calculated by actual power to be consumed by the entity divided by the maximum power of the entity. In addition, the minimum power gain can also be measured and reported.

5.5.4. Time Intervals

The standard must provide means for reporting the time interval for which an energy value is reported.

5.5.5. Energy Per Power State

The standard must provide means for reporting the received and provided energy for each individual Power State. This extends the requirements on Power State statistics described in Section 5.4.7.

5.6. Time Series of Measured Values

For some network management tasks, obtaining time series of measured values from entities, such as power, energy, etc., is required.

In general, time series measurements could be obtained in many different ways. Means should be provided to either push such values from the location where they are available to the management system or to have them stored locally for a sufficiently long period of time such that a management system can retrieve the full time series.

The following issues are to be considered when designing time series measurement and reporting functions:

  1. Which quantities should be reported?

  2. Which time interval type should be used (total, delta, sliding window)?

  3. Which measurement method should be used (sampled, continuous)?

  4. Which reporting model should be used (push or pull)?

The most discussed and probably most needed quantity is energy. But a need for others, such as power, can be identified as well.

There are three time interval types under discussion for accumulated quantities such as energy. They can be reported as total values, accumulated between the last restart of the measurement and a certain timestamp. Alternatively, energy can be reported as delta values between two consecutive timestamps. Another alternative is reporting values for sliding windows as specified in [IEC.61850-7-4].

For non-accumulative quantities, such as power, different measurement methods are considered. Such quantities can be reported using values sampled at certain timestamps or, alternatively, by mean values for these quantities averaged between two (consecutive) timestamps or over a sliding window.

Finally, time series can be reported using different reporting models, particularly push-based or pull-based. Push-based reporting can, for example, be realized by reporting power or energy values using the NETCONF protocol [RFC6241]. The NETCONF a protocol can also be used to realize pull-based reporting of time series.

For reporting time series of measured values, the following requirements have been identified. Further decisions concerning issues discussed above need to be made when developing concrete Energy Management standards.

5.6.1. Time Series of Energy Values

The standard must provide means for reporting time series of energy values. If the comparison of time series between multiple entities is required, then time synchronization between those entities must be provided (for example, with the Network Time Protocol [RFC5905]).

5.6.2. Time Series Interval Types

The standard must provide means for supporting alternative interval types. The requirement in Section 5.5.2 applies to every reported time value.

5.6.3. Time Series Storage Capacity

The standard should provide means for reporting the number of values of a time series that can be stored for later reporting.

6. Reporting on Lifecycle Management

Lifecycle information related to manufacturing energy costs, transport, recyclability, and end-of-life disposal impacts is part of what is called "embedded carbon." This information is considered to be an estimated value, which might not be implemented today in the network devices. It might be part of the vendor information, and to be collected from datasheets or databases. In accordance with ISO 14040/44, this information should be considered as part of the sustainable strategy related to energy efficiency. Also, refer to the ecodesign framework [(EU) 2024/1781] published in June by the European Commission.

6.1. Carbon Reporting

To report on carbon equivalents for global reporting, it is important to correlate the location where the specific entity/network element is operating with the corresponding carbon factor. Refer to the world emission factor from the International Energy Agency (IEA), electricity maps applications that reflect the carbon intensity of the electricity consumed, etc.

6.2. Energy Mix

Energy efficiency is not limited to reducing the energy consumption, it is common to include carbon free, solar energy, wind energy, cogeneration in the efficiency. The type of the sources of energy of the power is one criteria of efficiency. There are other dimensions that must visible: As many telecom locations include battery there is a requirement to known that the source come from a battery or directly from the grid...

7. Control of Entities

Many entities control their Power State locally. Other entities need interfaces for an Energy Management System to control their Power State.

A power supply is typically not self-managed by devices, and control of a power supply is typically not conducted as an interaction between an Energy Management System and the device itself. It is rather an interaction between the management system and a device providing power at its Power Outlets. Similar to Power State control, power supply control may be policy driven. Note that shutting down the power supply abruptly may have severe consequences for the device.

7.1. Provisioning Power States

The standard must provide means for provisioning Power States of entities.

When an Energy Object is set to a particular Power State, the represented device or component may be busy. The Energy Object should set the desired Power State and then update the actual Power State when the device or component changes. The standard must provide means to report the intented and applied Power States, with the Network Management Datastore Architecture (NMDA) [RFC8342]

7.2. Controlling Power SupplyProvisioning

The standard must provide means for switching a power supply off or turning a power supply on at Power Interfaces providing power to one or more devices.

7.3. Controlling Energy Saving and Optimization Functionalities

The standard must provide means for controlling energy saving and optimization functionalities and allocating the committed component resource (e.g., adjust fan speed, shutdown high speed interface) or committed device resource (e.g., multiple cards scheduling, multiple power module scheduling).

In addition, the standard must provide means to support both local management and network wide management based on energy saving functionality.

8. Management of oultet Entities

As discussed in Section 5, not all energy-related information may be available at the entity in question. Such information may be provided by other entities. This section groups the requirements for the discovery, the reporting and the control of information.

The intend is to summarize them in a table in section 9.

8.1. Discovery of Power inlet Entities

Energy consumption must not be accounted twice

8.1.1. Reporting on Other Entities

As discussed in Section 5, not all energy-related information may be available at the entity in question. Such information may be provided by other entities. This section covers only the reporting of information. See Section 8 for requirements on controlling other entities.

There are cases where a power supply unit switches power for several entities by turning power on or off at a single Power Outlet or where a power meter measures the accumulated power of several entities at a single power line. Consequently, it should be possible to report that a monitored value does not relate to just a single entity but is an accumulated value for a set of entities. All of the entities belonging to that set need to be identified.

8.1.2. Reports on Other Entities

The standard must provide means for an entity to report information on another entity.

8.1.3. Identity of Other Entities on Which Information Is Reported

For entities that report on one or more other entities, the standard must provide means for reporting the identity of other entities on which information is reported. Note that, in some situations, a manual configuration might be required to populate this information.

8.1.4. Reporting Quantities Accumulated over Multiple Entities

The standard must provide means for reporting the list of all entities from which contributions are included in an accumulated value.

8.1.5. List of All Entities on Which Information Is Reported

For entities that report on one or more other entities, the standard must provide means for reporting the complete list of all those entities on which energy-related information can be reported.

8.1.6. Content of Reports on Other Entities

For entities that report on one or more other entities, the standard must provide means for indicating what type or types of energy- related information can be reported, and for which entities.

8.2. Controlling Other Entities

This section specifies requirements for controlling Power States and power supply of entities by communicating with other entities that have the means for doing that control.

8.2.1. Controlling Power States of Other Entities

RFC6988 allow some entities have control over Power States of other entities, e.g., in Building automation case where a gateway to a building system may have the means to control the Power State of entities in the building that do not have an IP interface.

In this document, we assume all network devices have IP connectivity in the operator controlled environment. Therefore only an Energy Management System has control over Power States of other entities.

In addition, it is required that an entity that has its state controlled by the Energy Management System has the means to report the list of these other entities.

8.2.1.1. Control of Power States of Other Entities

The standard must provide means for an Energy Management System to send Power State control commands to an entity that controls the Power States of entities other than the entity to which the command was sent.

8.2.1.2. Identity of Other Power State Controlled Entities

The standard must provide means for reporting the identities of the entities for which the reporting entity has the means to control their Power States. Note that, in some situations, a manual configuration might be required to populate this information.

8.2.1.3. List of All Power State Controlled Entities

The standard must provide means for an entity to report the list of all entities for which it can control the Power State.

8.2.1.4. List of All Power State Controllers

The standard must provide means for an entity that receives commands controlling its Power State from other entities to report the list of all those entities.

8.2.2. Controlling Power Supply

Some entities may have control of the power supply of other entities, for example, because the other entity is supplied via a Power Outlet of the entity. For this and similar cases, means are needed to make this control accessible to the Energy Management System. This need is already addressed by the requirement in Section 6.2.

In addition, it is required that an entity that has its supply controlled by other entities has the means to report the list of these other entities. This need is already addressed by requirements in Sections 5.2.3 and 5.2.4.

9. Requirements extracted from proponents drafts

This section extracts and groups requirements from the documents of the proponents of the GREEN WG creation [GREEN-BOF], [sustainability-insights], [legacy-path] and [rfc6988bis-green]. The aim is to determine initial sets of requirements actionable at different levels of the framework presented below Section 9.5.

9.1. Operator'requirements from [charter-refinement] document

The table below is a copy of the operator'requirements table of [charter-refinement]. They are based on the inputs received from operators for the GREEN BoF [operators-inputs].

Table 1
category requirements note Priority
Observability Component granularity, e.g., per line-card, per-port Per component measurement 1
Observability Availability of information on the power consumption of the device, without needing instrumentation connected to the infrastructure Related to connected device case 1
Observability Triggering of alarms when consumption deviate from a nominal usage Alarm notification 1??
Observability Improvement of metering solutions (finer granularity, control of the energy efficiency and saving, interoperability, exposure) Standardized metering?? 1
Analysis Common definition of energy efficiency in network devices/components Standard metric 1
Analysis Common methodology of measurements for fair comparison Standard methodology 2
Analysis How to provide accurate figures (context of the measurement in terms of time period, location, traffic, etc Time based, location based visualization 2 ??
Analysis Database for decision in case of large data transfer Information Correlation 3
Analysis Ability of multi-layer analysis (e.g., IP plus optical) POI Use Case 3
Control& Mgmt To have devices with elastic power consumption according to the carried traffic Dynamic Energy Saving 2
Control& Mgmt Support of network-wide energy saving and optimization functions Network Level Mgmt 2
Control& Mgmt Support of network-wide control of energy optimization APIs, allowing external applications to optimize consumption Network Level Mgmt 2
Control& Mgmt Advanced sleep mode, needing some sort of low power mode when node is lightly utilized Dynamic Energy Saving 2
Control& Mgmt Ability to steer traffic based on power savings Traffic Engineering 4
Control& Mgmt Comparison of decision vs optimal case Intent based Concept 2
Control& Mgmt Synchronous query support Network Level Query 2
Inventory Management Inventory of power components (of devices, racks, etc) including together Component & Device Level 1
Interaction with other domain Inclusion of data center networks in the picture Data Center Case 3
Interaction with other domain Inclusion of data center networks in the picture Mobile Network Case 3
Sustainability & Carbon Emission Optimize the overall CO2 footprint (i.e., energy mix based on source type) facilitating the engineering of PoP More renewable energy More renewable energy 4
Sustainability & Carbon Emission Support GHG units Measurement Units 4
Sustainability & Carbon Emission Support Energy units More renewable energy 2 ??
Sustainability & Carbon EmissiCarbon, renewable 4    
Sustainability & Carbon Emission Accounting of legacy installed based GHG/energy Accounting Cost 4
Sustainability & Carbon Emission Track device/network Energy Consumption Before Operation Manufacturing, transport(weight, volume, package) 4

9.2. Requirements extracted from [legacy-path]

Table 2
category requirements note Priority
Inventory Management component control capacity (aka component max on/off frequency supported) Per component control 1 (i)
Analysis assess the gains of introducing eco-designed components in a device Device Level Mgmt 1 (ii)
Control& Mgmt comprehensive support of network-wide energy efficiency includes legacy devices Network Level Mgmt 1 (iii)

(i) Avoid control to break the component

(ii) the gain must be measurable

(iii) network-wide solution must include legacy devices and green-wg ready devices

9.3. Requirements from [rfc6988bis-green] draft Open Issues

Table 3
category requirements note Priority
Control& Mgmt Distinguish backup sources rfc6988bis battery 2
Inventory Management Reporting on Other Entities, typically smart PDU or PoE Fit in "Inventory of power components (of devices, racks, etc) including together" 2
Observability or Interaction with Other domain Room sensor (hvac...) Data Center Case 4
Observability flexible (future-proof) description of the nature of the sources of the energy used Standard metric 2

9.4. Requirements extracted from [sustainability-insights] uses cases

There are limited to energy consumption vs sustainability

Table 4
category requirements note Priority
Observability Provide near-real-time energy consumption to different device types, service types, and individual users Helps identify which devices or network functions are consuming more energy. 2
Migration or Upgrade Provide KPIs for energy efficiency parameters, enhance accuracy of upgrade decisions Helps make informed decisions about upgrades based on actual usage data.  
Recycling Report on percentage of recycled user devices and components. Enable comprehensive reporting and recycling efforts Major driver of the circular economy, transparency is key 4
Power Optimization Provide KPIs for energy efficiency parameters. Perform actions to reduce energy consumption Monitor network and application performance to optimize power usage 4
Control& Mgmt Switch off Stop and restart WiFi APs with the right time, space, and service granularity Save power consumption during periods when APs are not in use. 2

9.5. Framework Discussed During the BoF

The overall framework is shown in Figure 1.

       What needs to be standardized for Framework


(3) Network Domain Level :

(a)              (b)              (c)
Inventory        Monitor       +- DataSheets/DataBase and/or via API
Of identity      Energy        |  Metadata and other device/component
and Capability   Efficiency    |  /network related information:
     ^               ^         |
     |               |         |  .Power/Energy related metrics
     |               |         |  .information
     |               |         |  .origin of Energy Mix
     |               |         |  .carbon aware based on location
     |               |         |
     |               |         |
     |               |         |
     |               |         v
+--------------------------------------------------------------------+
|                   *                                                |
|     (2) controller   (collection, compute and aggregate?)          |
|                                                                    |
+--------------------------------------------------------------------+
             ^              ^                   ^ |
  (d)        |  (e)         |  (f)              | |(g)
  Inventory  |  Monitor     |  GREEN WG:        | |GREEN WG: Control
  Capability |  Traffic     |  Monitor power    | |(Energy saving
             |  & power     |  Proportion,      | |Functionality
             |  consumption |  Energy efficiency| |Localized mgmt/
             |              |  ratio, etc)      | |network wide mgmt)
             |              |                   | |
             |              |                   | |
             |              |                   | v
+--------------------------------------------------------------------+
|                                            *                       |
|                  (1) Device/Component Level                        |
|                                                                    |
| +---------+  +-----------+  +----------------+  +----------------+ |
| | (I)     |  | (II)      |  | (III)          |  | (IV)           | |
| | Network |  | Device    |  | Legacy Network |  | 'Attached'(PoE | |
| | Device  |  | Component |  | Device         |  | kind) Device   | |
| |         |  |           |  |                |  |                | |
| +---------+  +-----------+  +----------------+  +----------------+ |
+--------------------------------------------------------------------+

(*) Energy Efficiency Management Function is implemented inside the
device or in a controller

Figure 1: Framework discussed during the BoF

The main elements in the framework are as follows:

(a),(d) Inventory

(b),(c) GREEN Metrics

(b),(f) Monitor energy efficiency

(e) Monitor power consumption and traffic (IPPM WG throughput, traffic load, etc)

(g) Control Energy Saving

10. Use Cases

This section describes a number of relevant use cases with the purpose of elicit requirements for Energy Efficiency Management. This is a work in progress and additional use cases will be documented in next versions of this document. ## Selective reduction of energy consumption in network parts proportional to traffic levels Traffic levels in a network follow patterns reflecting the behavior of consumers. Those patterns show periodicity in the terms of the traffic delivered, that can range from daily (from 00:00 to 23:59) to seasonal (e.g., winter to summer), showing peaks and valleys that could be exploited to reduce the consumption of energy in the network proportionally, in case the underlying network elements incorporate such capabilities. The reduction of energy consumption could be performed by leveraging on sleep modes in components up to more extreme actions such as switching off network components or modules. Such decisions are expected to no impact on the service delivered to customers, and could be accompanied by traffic relocation and / or concentration in the network. For this use case, the following requirements apply: |category|requirements|note|Priority| |:----|:----|:----|:----| |Observability|Component granularity, e.g., per line-card, per-port|Per component measurement|1| |Observability|Availability of information on the power consumption of the device, without needing instrumentation connected to the infrastructure|Related to connected device case|1| |Analysis|Common definition of energy efficiency in network devices/components|Standard metric|1| |Analysis|Ability of multi-layer analysis (e.g., IP plus optical)|POI Use Case|3| |Control& Mgmt|To have devices with elastic power consumption according to the carried traffic|Dynamic Energy Saving|2| |Control& Mgmt|Advanced sleep mode, needing some sort of low power mode when node is lightly utilized|Dynamic Energy Saving|2| |Control& Mgmt|Ability to steer traffic based on power savings|Traffic Engineering|4| These requirements are under revision as this is a work in progress. ## Additional use cases To be completed in next versions. # Security Considerations

Controlling Power State and power supply of entities are considered highly sensitive actions, since they can significantly affect the operation of directly and indirectly connected devices. Therefore, all control actions addressed in Sections 6 and 8 must be sufficiently protected through authentication, authorization, and integrity protection mechanisms.

Entities that are not sufficiently secure to operate directly on the public Internet do exist and can be a significant cause of risk, for example, if the remote control functions described in Sections 6 and 8 can be exercised on those devices from anywhere on the Internet. The standard needs to provide means for dealing with such cases. One solution is providing means that allow the isolation of such devices, e.g., behind a sufficiently secured gateway. Another solution is to allow compliant implementations to disable sensitive functions, or to not implement such functions at all.

The monitoring of energy-related quantities of an entity as addressed in Sections 5 through 8 can be used to derive more information than just the received and provided energy; therefore, monitored data requires protection. This protection includes authentication and authorization of entities requesting access to monitored data as well as confidentiality protection during transmission of monitored data. Privacy of stored data in an entity must be taken into account. Monitored data may be used as input to control, accounting, and other actions, so integrity of transmitted information and authentication of the origin may be needed.

10.1. Secure Energy Management

The standard must provide privacy, integrity, and authentication mechanisms for all actions addressed in Sections 5 through 8. The security mechanisms must meet the security requirements detailed in Section 1.4 of [RFC3411].

10.2. Isolation of Insufficiently Secure Entities

The standard must provide means to allow the isolation of entities that are not sufficiently secure to operate on the public Internet, e.g., behind a gateway that implements sufficient security that the vulnerable entities are not directly exposed to the Internet.

10.3. Optional Restriction of Functions

The standard must allow compliant implementations to disable sensitive functions, or to not implement such functions at all, when operating in environments that are not sufficiently secured. This applies particularly to the control functions described in Sections 6 and 8.

11. Security

Adding new interfaces on devices increase attack surfaces. Devices have brief variation of power consumption due their internal works. Reducing the power available may reduce their routing capacity which may reduce network performance and resiliency.

12. IANA Considerations

This document has no IANA actions.

13. Acknowledgments

14. Open Issues

o Do we need to keep a reference to the MIB object entPhysicalUUID (in section 4.4 from ENTITY-MIB v4) in case of legacy device (MIB)?

o The EMAN requirements and EMAN framework had a lot of emphasis on the "Reporting on Other Entities", typically smart PDU or PoE. Is this important? Should this be removed? Should it be addressed in a future charter? This is text about "Sections 7 and 8 contain requirements specific to Energy Management. Due to the nature of power supply, some monitoring and control functions are not conducted by interacting with the entity of interest but rather with other entities, for example, entities upstream in a power distribution tree."

Expressed differently: Out of scope for the short term approach of EMAN framework enhancements, but might be good to call it out, EMAN doesn't include mechanisms for integrating occupancy sensors or user behavior analytics, which can be critical for optimizing HVAC, lighting, and other systems for energy efficiency. This is a key aspect for Smart Buildings and Data Centers energy efficiency metrics.

o It's not clear whether we need new Power State (Set)? Maybe not but we need to explain the mapping of existing energy efficient features to specific Power States.

o basic (scalar) units are not enough to describe Power Data Unit capabilities and/or output. We need a more complex structure (which might already exist?) to cover and combine meanings (that I copied from the chats) like CO2 footprint, clean energy, mix, renewable. as an example, this should help to describe reduction of energy consumption and the increase of renewable energy consumption

o Enhance EMAN framework, to support a more robust and comprehensive Energy Efficiency Strategy. Let devices report whatever they can using existing interfaces, without waiting until they implement new capabilities determined by new or existing standards. Including the capability to integrate with external data sources (for example, for devices that don't have the capability or reporting any energy-related metrics) such as vendor datasheets that provide energy consumption. Use case => upgrading a device for better Energy Efficiency Management. Not sure whether framework-related requirements should be covered here.

o Leveraging existing devices modularity to introduce eco-designed components in the networks while being able to assess the gains in sustainability. https://datatracker.ietf.org/doc/html/draft-stephan-legacy-path-eco-design-01 https://github.com/emile22/sustainability

o Discuss the need to reflect component on/off frequency capacity (in YANG) to avoid too intensive power on/off.

o Discuss the need to support a description of the different nature of the sources of the energy used (mix). It should be flexible are the types of sources might augment in the future.

o Company's SBTi approved decarbonization plan and how to link it to GREEN WG scope, short/mid vs long term.

The Science Based Targets initiative(SBTi)[https://sciencebasedtargets.org] defines and promotes best practice in science-based target setting. Offering a range of target-setting resources and guidance, the SBTi independently assesses and approves companies targets in line with its strict criteria.

Open issue, https://github.com/marisolpalmero/GREEN-bof/issues/88

o Consideration to include in scope, allocate/compute and report the energy spent on behalf of a particular customer/user. Open issue, marisolpalmero/GREEN-bof#89

15. References

15.1. Normative References

[IEC.61850-7-4] International Electrotechnical Commission, "Communication networks and systems for power utility automation -- Part 7-4: Basic communication structure -- Compatible logical node classes and data object classes", March 2010.

[IEC.62053-21] International Electrotechnical Commission, "Electricity metering equipment (a.c.) -- Particular requirements -- Part 21: Static meters for active energy (classes 1 and 2)", January 2003.

[IEC.62053-22] International Electrotechnical Commission, "Electricity metering equipment (a.c.) -- Particular requirements -- Part 22: Static meters for active energy (classes 0,2 S and 0,5 S)", January 2003.

[IEEE-100] IEEE, "The Authoritative Dictionary of IEEE Standards Terms, IEEE 100, Seventh Edition", December 2000.

[IEEE-1621] Institute of Electrical and Electronics Engineers, "IEEE 1621-2004 - IEEE Standard for User Interface Elements in Power Control of Electronic Devices Employed in Office/Consumer Environments", 2004.

[ATIS-0600015.03.2013] ATIS, "ATIS-0600015.03.2013: Energy Efficiency for Telecommunication Equipment: Methodology for Measurement and Reporting for Router and Ethernet Switch Products", 2013.

[ETSI-ES-203-136] ETSI, "ETSI ES 203 136: Environmental Engineering (EE); Measurement methods for energy efficiency of router and switch equipment", 2017, <https://www.etsi.org/deliver/ etsi_es/203100_203199/203136/01.02.00_50/ es_203136v010200m.pdf>.

[ITUT-L.1310] ITU-T, "L.1310 : Energy efficiency metrics and measurement methods for telecommunication equipment", 2020, https://www.itu.int/rec/T-REC-L.1310/en.

15.2. Informative References

[IEC.60050] International Electrotechnical Commission, "Electropedia: The World's Online Electrotechnical Vocabulary", 2013, http://www.electropedia.org/iev/iev.nsf/ welcome?openform.

[ITU-M.3400] International Telecommunication Union, "ITU-T Recommendation M.3400 -- Series M: TMN and Network Maintenance: International Transmission Systems, Telephone Circuits, Telegraphy, Facsimile and Leased Circuits -- Telecommunications Management Network - TMN management functions", February 2000.

16. Appendix

This appendix should be removed in the next version

16.1. In Preparation of the GREEN BoF at IETF 120

The EMAN (Energy MANagement) working group (WG), created in 2010 and now concluded, has produced multiples RFCs

  * RFC7603, Energy Management (EMAN) Applicability Statement

  * RFC7577, Definition of Managed Objects for Battery Monitoring

  * RFC7460, Monitoring and Control MIB for Power and Energy

  * RFC7461, Energy Object Context MIB

  * RFC7326, Energy Management Framework

  * RFC6988, Requirements for Energy Management

  * RFC6933, Entity MIB (Version 4)

Note also that some other energy-related MIB modules have been created, but not by the EMAN Working Group

  * RFC3433, Entity Sensor MIB module

  * RFC3621, Power Ethernet MIB modules

  * RFC1628, UPS Power Monitoring MIB module

  * LLDP MIB module and LLDP MED MIB module

Due to limitations regarding Writeable MIB module, one IESG statement published in 2014 encourages the use the NETCONF/YANG standards for configuration. Based on the YANG modules developments, three MIB modules (Entity MIB module, Entity Sensor MIB module, Entity State MIB module) have been converted into the "YANG Data Model for Hardware Management" RFC8348.

However, Power and Energy Monitoring and Control MIB modules has not been converted yet into YANG modules.

Eleven years after the EMAN requirements RFC 6988 publication, this document re-evaluates the energy-related requirements, as a preparation for the GREEN BoF at IETF 120.

16.2. High-level Differences with RFC6988

The following section will delve into the specific details but from a high level point of view, the differences between this document and the RFC6988 are:

  • New definition for "Energy Efficiency Management"

  • A focus towards YANG, and not any longer on MIB modules

  • As a consequence from the previous point, the ENTITY-MIB v4 RFC6933 is replaced by the Hardware YANG module RFC8348

  • battery management is removed (as batteries haves some self-optimization features these days)

  • Less focus on the Power over Ethernet management

  • A focus on reporting lifecycle management, considering energy and transformation towards carbon awareness

17. Informative References

[GREEN-BOF]
"BOF proposal for GREEN WG Creation", , <https://github.com/marisolpalmero/GREEN-bof>.
[I-D.ietf-ivy-network-inventory-yang]
Yu, C., Belotti, S., Bouquier, J., Peruzzini, F., and P. Bedard, "A YANG Data Model for Network Inventory", Work in Progress, Internet-Draft, draft-ietf-ivy-network-inventory-yang-03, , <https://datatracker.ietf.org/doc/html/draft-ietf-ivy-network-inventory-yang-03>.
[operators-inputs]
"Input from Operators to GREEN BoF", , <https://datatracker.ietf.org/meeting/120/materials/slides-120-green-input-from-operators-to-green-bof-01>.
[RFC3411]
Harrington, D., Presuhn, R., and B. Wijnen, "An Architecture for Describing Simple Network Management Protocol (SNMP) Management Frameworks", STD 62, RFC 3411, DOI 10.17487/RFC3411, , <https://www.rfc-editor.org/rfc/rfc3411>.
[RFC5905]
Mills, D., Martin, J., Ed., Burbank, J., and W. Kasch, "Network Time Protocol Version 4: Protocol and Algorithms Specification", RFC 5905, DOI 10.17487/RFC5905, , <https://www.rfc-editor.org/rfc/rfc5905>.
[RFC6241]
Enns, R., Ed., Bjorklund, M., Ed., Schoenwaelder, J., Ed., and A. Bierman, Ed., "Network Configuration Protocol (NETCONF)", RFC 6241, DOI 10.17487/RFC6241, , <https://www.rfc-editor.org/rfc/rfc6241>.
[RFC8342]
Bjorklund, M., Schoenwaelder, J., Shafer, P., Watsen, K., and R. Wilton, "Network Management Datastore Architecture (NMDA)", RFC 8342, DOI 10.17487/RFC8342, , <https://www.rfc-editor.org/rfc/rfc8342>.
[RFC8345]
Clemm, A., Medved, J., Varga, R., Bahadur, N., Ananthakrishnan, H., and X. Liu, "A YANG Data Model for Network Topologies", RFC 8345, DOI 10.17487/RFC8345, , <https://www.rfc-editor.org/rfc/rfc8345>.
[RFC8348]
Bierman, A., Bjorklund, M., Dong, J., and D. Romascanu, "A YANG Data Model for Hardware Management", RFC 8348, DOI 10.17487/RFC8348, , <https://www.rfc-editor.org/rfc/rfc8348>.

Authors' Addresses

Emile Stephan
Orange
Marisol Palmero
Cisco Systems, Inc.
Benoit Claise
Huawei
Qin Wu
Huawei
Luis M. Contreras
Telefonica